3 - 15
3 Communications Data for CompoWay/F
E5C-T Digital Controllers Programmable Type Communications Manual (H186)
3-1 Variable Area (Setting Range) List
3
Variable
type
Address Parameter name Setting (monitor) value Level
C3 (83) 0050 Auxiliary Output 1
Assignment
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Heater alarm
H'00000008 (8): HB alarm
H'00000009 (9): HS alarm
H'0000000A (10): Input error
H'0000000B (11): Program end output
H'0000000C (12): Stage output
H'0000000D (13): RUN output
H'0000000E (14): Time signal 1 output
H'0000000F (15): Time signal 2 output
H'00000010 (16): Integrated alarm
H'00000011 (17): Work bit 1
H'00000012 (18): Work bit 2
H'00000013 (19): Work bit 3
H'00000014 (20): Work bit 4
H'00000015 (21): Work bit 5
H'00000016 (22): Work bit 6
H'00000017 (23): Work bit 7
H'00000018 (24): Work bit 8
Advanced
function
setting
C3 (83) 0051 Auxiliary Output 2
Assignment
H'00000000 to H'00000018 (0 to 24)
Note: Same as for the Auxiliary Output 1 Assignment
parameter.
C3 (83) 0055 Alarm SP
Selection
H'00000000 (0): Set point during SP ramp
H'00000001 (1): Set point
Advanced
function
setting
C3 (83) 0056 Auxiliary Output 3
Assignment
H'00000000 to H'00000016 (0 to 22)
Note: Same as for the Auxiliary Output 1 Assignment
parameter.
C3 (83) 0057 Close/Floating H'00000000 (0): Floating
H'00000001 (1): Close
Initial
setting
C3 (83) 0058 Travel Time H'00000001 to H'000003E7 (1 to 999)
C3 (83) 0059 PV Dead Band H'00000000 to H'0000270F (0 to 9999)
Advanced
function
setting
C3 (83) 005B Manual MV Limit
Enable
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83) 005C Direct Setting of
Position
Proportional MV
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83) 005D AT Calculated Gain H'00000001 to H'00000064 (0.1 to 10.0)
C3 (83) 005E AT Hysteresis H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 9.99 for analog input)
C3 (83) 005F Limit Cycle MV
Amplitude
H'00000032 to H'000001F4 (5.0 to 50.0)
C3 (83) 0063 SP Tracking H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83) 0065 PID Set Automatic
Selection Data
H'00000000 (0): PV
H'00000001 (1): DV
H'00000002 (2): SP
Vue de la page 60