3 Communications Data for CompoWay/F
3 - 24
E5C-T Digital Controllers Programmable Type Communications Manual (H186)
C5 (85) 0004 PID 1 MV Lower Limit Standard control or position proportional
(closed): H'FFFFFFCE to MV upper limit 0.1
(5.0 to MV upper limit 0.1)
Heating/cooling control: H'FFFFFBE6 to
H'00000000 (105.0 to 0.0)
PID Setting
C5 (85) 0005 PID 1 Automatic
Selection Range
Upper Limit
Temperature input: H'FFFFF831 to
H'0000270F (1999 to 9999)
Analog input: H'FFFFFFCE to H'0000041A
(5.0 to 105.0)
C5 (85) 0007 PID 1 LBA Detection
Time
H'00000000 to H'0000270F (0 to 9999)
C5 (85) 0008 PID 1 Proportional
Band (Cooling)
H'00000001 to H'0000270F (0.1 to 999.9)
C5 (85) 0009 PID 1 Integral Time
(Cooling)
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is
0.1 s.)
C5 (85) 000A PID 1 Derivative Time
(Cooling)
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is
0.1 s.)
C5 (85) 000B PID 1 Dead Band Temperature input: H'FFFFF831 to
H'0000270F (1999 to 999.9)
Analog input: H'FFFFF831 to H'0000270F
(19.99 to 99.99)
C5 (85) 000C PID 1 Manual Reset
Value
H'00000000 to H'000003E8 (0.0 to 100.0)
C5 (85) 0010
PID 2 Proportional
Band
H'00000001 to H'0000270F (0.1 to 999.9)
to to
C5 (85) 001C PID 2 Manual Reset
Value
H'00000000 to H'0000270F (0 to 9999)
C5 (85) 0020 PID 3 Proportional
Band
H'00000001 to H'0000270F (0.1 to 999.9)
to to
C5 (85) 002C PID 3 Manual Reset
Value
H'00000000 to H'0000270F (0 to 9999)
C5 (85) 0030 PID 4 Proportional
Band
H'00000001 to H'0000270F (0.1 to 999.9)
to to
C5 (85) 003C PID 4 Manual Reset
Value
H'00000000 to H'0000270F (0 to 9999)
C5 (85) 0040 PID 5 Proportional
Band
H'00000001 to H'0000270F (0.1 to 999.9)
to to
C5 (85) 004C PID 5 Manual Reset
Value
H'00000000 to H'0000270F (0 to 9999)
C5 (85) 0050 PID 6 Proportional
Band
H'00000001 to H'0000270F (0.1 to 999.9)
to to
C5 (85) 005C PID 6 Manual Reset
Value
H'00000000 to H'0000270F (0 to 9999)
Variable
type
Address Parameter name Setting (monitor) value Level