2 CompoWay/F Communications Procedures
2 - 12
E5C-T Digital Controllers Programmable Type Communications Manual (H186)
This service writes in order the contents of specified addresses to a variable area.
Service Request PDU
Service Response PDU
(1) Variable Type and Write Start Address
For details on variable types and write start addresses, refer to Section 3 Communications Data for
CompoWay/F.
(2) Bit Position
Bit access is not supported. Fixed to “00.
(3) Number of Write Data Items (Variable Type + Write Address + Bit Position + Write Data
Counted As 1 Item)
Note: The following table gives the maximum number of write data items when double-word data and word data
are used together.
1101 Area type error The variable type is wrong.
110B
Response too long The number of elements exceeds
the maximum.
1100 Parameter error Bit position is not "00."
2203 Operation error Non-volatile memory error
2-3-4 Composite Write to Variable Area
Write data length Number of write data items
Double word (variable types C0, C1, C3, C4, C5, or DA) 12 max.
Word (variable types 80, 81, 83, 84, 85, or 9A) 17 max.
Composite Write Composite Write
Double word
(variable types C0,
C1, C3, C4, C5, or
DA)
Word
(variable types 80,
81, 83, 84, 85, or 9A)
Double word
(variable types C0,
C1, C3, C4, C5, or
DA)
Word
(variable types 80,
81, 83, 84, 85, or 9A)
12 0 5 10
12 1 4 11
11 2 3 12
10 3 3 13
94 214
95 115
Response code Error name Cause
22
MRC
SRC
0113
00
224
00
224
Variable
type
Write
address
Variable
type
Write data
Write data
Write
address
Bit
position
Bit
position
Number of elements ×8 or 4
Number of elements ×8 or 4
MRC SRC
0113
22 4
Response
code