3 Communications Data for CompoWay/F
3 - 16
E5C-T Digital Controllers Programmable Type Communications Manual (H186)
C3 (83) 0066 PID Set Automatic
Selection
Hysteresis
H'0000000A to H'0000270F (0.10 to 99.99) Advanced
function
setting
C3 (83) 0067 PV Rate of Change
Calculation Period
H'00000001 to H'000003E7 (1 to 999)
C3 (83) 0068 Heating/Cooling
Tuning Method
H'00000000 (0): Same (Same as for heating.)
H'00000001 (1): Linear
H'00000002 (2): Air cooling
H'00000003 (3): Water cooling
C3 (83) 006C Extraction of
Square Root
Enable
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83) 006D PF Setting H'00000000 (0): Disabled.
H'00000001 (1): Run
H'00000002 (2): RESET
H'00000003 (3): RUN/RESET
H'00000004 (4): Hold/clear hold
H'00000005 (5): Advance
H'00000006 (6): 100% AT execute/cancel
H'00000007 (7): 40% AT execute/cancel
H'00000008 (8): All PID 100% AT execute/cancel
H'00000009 (9): All PID 40% AT execute/cancel
H'0000000A (10): Alarm latch cancel
H'0000000B (11): Auto/manual switch
H'0000000C (12): Monitor/setting item
H'0000000D (13): Digit shift key
C3 (83) 006E Monitor/Setting
Item 1
H'000000000 (0): Disabled
H'000000001 (1): PV/SP/Program No. monitor or segment
No. monitor
H'000000002 (2): PV/SP/MV (heating) (valve opening for
Position-proportional Models)
H'000000003 (3): PV/SP/MV (cooling)
H'000000004 (4): PV/SP/Remaining segment time
H'000000005 (5): Program No.
H'000000006 (6): Segment No. monitor
H'000000007 (7): Remaining standby time monitor
H'000000008 (8): Elapsed program time monitor
H'000000009(9): Remaining program time monitor
H'00000000A (10): Elapsed segment time monitor
H'00000000B (11): Remaining segment time monitor
H'00000000C (12): Program execution repetitions monitor
H'00000000D (13): Proportional band
H'00000000E (14): Integral time
H'00000000F (15): Derivative time
H'000000010 (16): Proportional band (cooling)
H'000000011 (17): Integral time (cooling)
H'000000012 (18): Derivative time (cooling)
H'000000013 (19): Alarm value 1
H'000000014 (20): Alarm value upper limit 1
H'000000015 (21): Alarm value lower limit 1
H'000000016 (22): Alarm value 2
H'000000017 (23): Alarm value upper limit 2
H'000000018 (24): Alarm value lower limit 2
H'000000019 (25): Alarm value 3
H'00000001A (26): Alarm value upper limit 3
H'00000001B (27): Alarm value lower limit 3
H'00000001C (28): Alarm value 4
H'00000001D (29): Alarm value upper limit 4
H'00000001E (30): Alarm value lower limit 4
Variable
type
Address Parameter name Setting (monitor) value Level