Unication E5 Spécifications Page 102

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 186
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 101
5 Communications Data for Modbus
5 - 8
E5C-T Digital Controllers Programmable Type Communications Manual (H186)
Address
Parameter name Setting (monitor) value Level
Four-byte
mode
Two-byte
mode
0C00 2C00 Input Type H'00000000 (0): Pt (200 to 850°C/300 to 1500°F)
H'00000001 (1): Pt (199.9 to 500.0°C/199.9 to 900.0°F)
H'00000002 (2): Pt (0.0 to 100.0°C/0.0 to 210.0
°F
)
H'00000003 (3): JPt (199.9 to 500.0°C/199.9 to 900.0°F)
H'00000004 (4): JPt (0.0 to 100.0°C/0.0 to 210.0
°F
)
H'00000005 (5): K (200 to 1300°C/300 to 2300°F)
H'00000006 (6): K (20.0 to 500.0°C/0.0 to 900.0°F)
H'00000007 (7): J (100 to 850°C/100 to 1500°F)
H'00000008 (8): J (20.0 to 400.0°C/0.0 to 750.0°F)
H'00000009 (9): T (200 to 400°C/300 to 700°F)
H'0000000A (10): T (199.9 to 400.0°C/199.9 to 700.0°F)
H'0000000B (11): E (200 to 600°C/300 to 1100°F)
H'0000000C (12): L (100 to 850°C/100 to 1500°F)
H'0000000D (13): U (200 to 400°C/300 to 700°F)
H'0000000E (14): U (199.9 to 400.0°C/199.9 to 700.0°F)
H'0000000F (15): N (200 to 1300°C/300 to 2300°F)
H'00000010 (16): R (0 to 1700°C/0 to 3000°F)
H'00000011 (17): S (0 to 1700°C/0 to 3000°F)
H'00000012 (18): B (100 to 1800°C/300 to 3200°F)
H'00000013 (19): W (0 to 2,300°C/0 to 3,200°F)
H'00000014 (20): PLII (0 to 1,300°C/0 to 2,300°F)
H'00000015 (21): Infrared temperature sensor (K 140°F/60°C)
H'00000016 (22): Infrared temperature sensor (K 240°F/120°C)
H'00000017 (23): Infrared temperature sensor (K 280°F/140°C)
H'00000018 (24): Infrared temperature sensor (K 440°F/220°C)
H'00000019 (25): 4 to 20 mA
H'0000001A (26): 0 to 20 mA
H'0000001B (27): 1 to 5 V
H'0000001C (28): 0 to 5 V
H'0000001D (29): 0 to 10 V
Initial setting
0C02 2C01 Temperature Unit H'00000000 (0): °C
H'00000001 (1): °F
0C12 2C09 Scaling Lower Limit H’FFFFF831 to scaling upper limit 1
(1999 to scaling upper limit 1)
0C16 2C0B Scaling Upper Limit Scaling lower limit + 1 to H'0000270F
(Scaling lower limit + 1 to 9999)
0C18 2C0C Decimal Point H'00000000 to 00000003 (0 to 3)
0C22 2C11 Burnout Method H'00000000 (0): Upscale
H'00000001 (1): Downscale
Initial setting
0D06 2D03 Control Output 1 Signal H'00000000 (0): 4 to 20 mA
H'00000001 (1): 0 to 20 mA
0D08 2D04 Control Output 2 Signal H'00000000 (0): 4 to 20 mA
H'00000001 (1): 0 to 20 mA
0D1E 2D0F SP Upper Limit The range of values (without decimal point) is as follows:
Temperature input: SP lower limit + 1 to Input range upper limit
Analog input: SP lower limit + 1 to Scaling upper limit
0D20 2D10 SP Lower Limit The range of values (without decimal point) is as follows:
Temperature input: Input range lower limit to SP upper limit 1
Analog input: Scaling lower limit to SP upper limit 1
0D22 2D11 Standard or Heat-
ing/Cooling
H'00000000 (0): Standard
H'00000001 (1): Heating and cooling
0D24 2D12 Direct/Reverse Operation H'00000000 (0): Reverse operation
H'00000001 (1): Direct operation
0D26 2D13 Close/Floating H'00000000 (0): Floating
H'00000001 (1): Close
0D28 2D14 PID ON/OFF H'00000000 (0): ON/OFF
H'00000001 (1): 2 PID control
Vue de la page 101
1 2 ... 97 98 99 100 101 102 103 104 105 106 107 ... 185 186

Commentaires sur ces manuels

Pas de commentaire