3 Communications Data for CompoWay/F
3 - 4
E5C-T Digital Controllers Programmable Type Communications Manual (H186)
Note: The alarm function can also be used in Digital Controllers without auxiliary output terminals. In this case,
confirm alarm occurrences via the status data.
*1 The parameter for the currently selected PID set will be accessed. For setup area 1, however, the currently
selected PID set is fixed at PID1.
Variable
type
Address Parameter name Setting (monitor) value Level
C1 (81) 0000 Operation/Adjustm
ent Protect
H'00000000 (0) to H'00000005 (5)
0: No control
1: Operation level (PV displayed, PV/SP allowed,
others allowed), program level allowed,
adjustment level allowed, PID setting level
prohibited
2: Operation level (PV displayed, PV/SP allowed,
others allowed), program level allowed,
adjustment level prohibited, PID setting level
prohibited
3: Operation level (PV displayed, PV/SP allowed,
others allowed), program level prohibited,
adjustment level prohibited, PID setting level
prohibited
4: Operation level (PV displayed, PV/SP allowed,
others prohibited), program level prohibited,
adjustment level prohibited, PID setting level
prohibited
5: Operation level (PV displayed, PV/SP displayed,
others prohibited), program level prohibited,
adjustment level prohibited, PID setting level
prohibited
Protect
C1 (81) 0001 Initial
Setting/Communic
ations Protect
H'00000000 (0): Move to initial
setting/communications setting
level is allowed. (Move to advanced
function setting level is displayed.)
H'00000001 (1): Move to initial
setting/communications setting
level is allowed. (Move to advanced
function setting level is not
displayed.)
H'00000002 (2): Move to initial
setting/communications setting
level is prohibited.
C1 (81) 0002 Setting Change
Protect
H'00000000 (0): OFF (Changing of setup on
Controller display is allowed.)
H'00000001 (1): ON (Changing of setup on
Controller display is prohibited.)
C1 (81) 000D Heater Burnout
Detection 1
H'00000000 to H'000001F4 (0.0 to 50.0) Adjustment
C1 (81) 0012 Process Value
Input Shift
H'FFFFF831 to H'0000270F (1999 to 9999)
C1 (81) 0013 Process Value
Slope Coefficient
H'00000001 to H'0000270F (0.001 to 9.999)
C1 (81)
0015
Proportional
Band
*1
H'0000001 to H'0000270F (0.1 to 999.9)