7 - 5
7 Component Communications
E5C-T Digital Controllers Programmable Type Communications Manual (H186)
7-1 Component Communications
7
7-1-3 E5@C-T Controller Setup
SP Calculations (Fixed-value Controllers Only)
The set point of a slave can be calculated from the fixed SP or program SP of the master as shown
below. The slave performs the calculation only during operation. The value is not written to the slave if it
exceeds the set point limiter.
During operation: Slave SP = Master SP × SP Slope + SP Offset
When stopped: Slave SP = Master SP
Communications Setting Level
Display condition: The Protocol Setting parameter must be set to cmp and the Communications Unit No.
parameter must not be set to 0 (0 = master).
* The decimal point position depends on the Decimal Point parameter setting.
Parameter name
Displayed
characters
Setting range Unit Default
SP Slope sps 0.001 to 9.999 None 1.000
SP Offset spos Temperature input: 199.9 to 999.9
Analog input: 1,999 to 9,999*
EU 0.0